Colocation Features and Benefits
Datacenter Features and Benefits
- Redundant Tier 1 DS3 Backbone
- Redundant Tier 1 Providers
- Redundant Back Up Power Infrastructure
- Redundant Security
- 100Mb Burstable Connection (Gigabit Connections Available)
- Climate Control
- Redundant Security and Access
- 24 x 7 network monitoring
- 24 x 7 emergency help
- Customer testimonials
- Reliable and accurate technical help
Colocation Redundant Back Up Power Infrastructure
- 1,000 to 1,600 amps at 480 volt total capacity, depending on site
- 80 to 85 watts per square foot including HVAC
- 120/208V AC and -48V DC available
- 100% generator backup
- Generator capacity 600-2000 KW
- Size of fuel tank 1,000 to 2,000 gallons
- Generator - both auto start and auto transfer -Isolation bypass feature on automatic transfer switch
- Minimum 24-hour run time fuel capacity - 2-hour response for fuel delivery
- UPS backup power system
- Voltage output 480 transformed to 120/208 V
- 48 volt DC Battery Plant
- 1200 amp expandable to 4800 amp
- 2-hour battery reserve non-redundant, 4 hours redundant
- A/B Power feeds available
- Grounding in accordance with NFPA 70
Colocation Redundant Security and Monitoring
- 24/7 security management via the Security Operations Center (SOC)
- Remote camera monitoring 24/7, backed by digital recordings on file for 45 days
- Access to equipment area 24/7 days via card key and pass code only
- Escort services 24/7 at sites with non-secured equipment areas
- Locking cabinets and/or cages
- Full CCTV surveillance
- Falcon equipment monitoring system supported by Switch and Data's 24x7 operations center
Colocation Climate Control
- 80 to 85 watts per square foot including HVAC
- Under-floor cooling provided by computer-room grade equipment
- Cooling not less than 150 BTU/h per square foot with an N+1 redundancy
- Temperature is maintained at 72 degrees F dry bulb at ASHRAE 1%
- Redundant power supplied to HVAC systems by diesel generators if there is a power interruption
- 30% to 60% humidity non-condensing. Humidity control delivered through ATS/Liebert units via infra-red humidifier
Colocation Facility Features
- Open space for cabinets
- Private cages available
- Meet all code specifications for safety and electrical grounding, per NFPA 70
- Open, accessible ceiling
- DC power and communication cabling tray pathways
- Optical fiber guide conveyance system
- Heavy load freight elevators or loading dock access to the space
- Comprehensive and flexible cabling infrastructure
- Top-quality, electrostatic dissipative raised floor tiles designed for 100 psf, and in some facilities 250 lbs. psf, floor load
Colocation Fire Detection and Suppression
- Pre-action sprinkler rated for telecommunication equipment/computer room
- Integrated smoke/heat detector system
- Under-floor leak detection system
Contact a Business Sales Consultant Today!
1.877.422.5224
VIP Support - 1.888.807.7778
|